Titre: | Caractérisation numérique d’une prise de terre à géométrie complexe |
Auteur(s): | Lefouili, Moussa |
Mots-clés: | Default Radiation Electromagnetic field Hertzian dipoles Transient Images method Grounding system |
Date de publication: | 12-avr-2018 |
Résumé: | In this work a new approach for detection and localization of fault on buried conductor is
developed. This study is based on the analysis of electromagnetic field with and without
fault. The theoretical expressions in time domain of electromagnetic field radiated by
electric dipole in infinite conductive medium are used, in the half space the interface soilair
is taken into account using modified method of images. The computation results are
based on a general formulation, in time domain, which permits the observation points in air
or soil. The study revealed that both electric and magnetic fields can be used to detect
opening in current-carrying conductors. |